dc.contributor.advisorSanango Fernández, Juan Bautista-
dc.contributor.authorVillegas Aldeán, María Belén-
dc.contributor.authorTrelles Lituma, Gabriela Marisol-
dc.date.accessioned2023-05-25T19:07:17Z-
dc.date.available2023-05-25T19:07:17Z-
dc.date.issued2023-05-24-
dc.identifier.urihttp://dspace.ucuenca.edu.ec/handle/123456789/41962-
dc.descriptionPara determinar la cantidad de generación distribuida que se puede albergar en los alimentadores de distribución de media tensión de la EMPRESA ELÉCTRICA REGIONAL CENTRO SUR C.A. (CENTROSUR) se propone una metodología que permita calcular la Capacidad de Alojamiento Fotovoltaica (por sus siglas en inglés “Photovoltaic Hosting Capacity”, PVHC). Esta capacidad no es un cálculo fijo con un único resultado, sino un rango de valores definidos por; los datos de entrada de la red, criterios y límites establecidos en estándares internacionales y normativa local. Se plantea cinco criterios de análisis, que permiten determinar la PVHC del alimentador. La base de análisis corresponde a una metodología híbrida iterativa y determinista basada en análisis de series temporales, que consiste en un procedimiento sistemático de inserción de Sistemas Fotovoltaicos (SFV) y verificación de los parámetros eléctricos de la red; esto se realiza mediante simulaciones usando scripts desarrollados en lenguaje de programación Python; que permitirán ejecutar simulaciones de flujo de potencia y cortocircuito en el paquete de análisis de sistemas de distribución; CYMDIST, del software CYME. Las simulaciones se realizan con cantidades de generación activa de los SFV que se incrementa a pasos determinados hasta un límite establecido sujeto a configuración. Como resultados de las simulaciones se presentan gráficas que identifican zonas de seguridad de penetración de SFV, así como los niveles de penetración mínimo y máximo para diferentes escenarios de instalación.en_US
dc.description.abstractIn order to determine the amount of distributed generation that can be accommodated in the medium voltage distribution feeders of EMPRESA ELÉCTRICA REGIONAL CENTRO SUR C.A. (CENTROSUR), a methodology is proposed to calculate the Photovoltaic Hosting Capacity (PVHC). This capacity is not a fixed calculation with a single result, but a range of values defined by; the grid input data, criteria and limits established in international standards and local regulations. Five analysis criteria are proposed to determine the PVHC of the feeder. The basis of analysis corresponds to a hybrid iterative and deterministic methodology based on time series analysis, which consists of a systematic procedure of insertion of Photovoltaic Systems (PVS) and verification of the electrical parameters of the grid; this is done through simulations using scripts developed in Python programming language; which will allow running power flow and short circuit simulations in the distribution systems analysis package; CYMDIST, of the CYME software. The simulations are performed with active generation quantities of the SFVs increasing at given steps up to a set limit subject to configuration. As results of the simulations, graphs are presented that identify SFV penetration safety zones, as well as minimum and maximum penetration levels for different installation scenarios.en_US
dc.description.uri0000-0002-3684-6134en_US
dc.formatapplication/pdfen_US
dc.format.extent88 páginas-
dc.language.isospaen_US
dc.publisherUniverisdad de Cuencaen_US
dc.relation.ispartofTE;501-
dc.rightsAttribution-NonCommercial-NoDerivatives 4.0 Internacional*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/*
dc.subjectIngeniería Eléctricaen_US
dc.subjectRedesen_US
dc.subjectFotovoltajeen_US
dc.subject.otherSimulacionesen_US
dc.titleCapacidad de alojamiento con generación distribuida en alimentadores de MT de la Empresa Eléctrica Centrosuren_US
dc.title.alternativeCapacidad de Alojamiento con Generación Distribuida en Alimentadores de MT de la Empresa Eléctrica CENTROSURen_US
dc.typedraften_US
dcterms.descriptionIngeniero Eléctricoen_US
dcterms.spatialCuencaen_US
dc.rights.accessRightsopenAccessen_US
Appears in Collections:Tesis de Pregrado

Files in This Item:
File Description SizeFormat 
Trabajo-de-Titulación.pdfVersión presentada (texto completo)7.61 MBAdobe PDFView/Open


This item is protected by original copyright



This item is licensed under a Creative Commons License Creative Commons

 

Centro de Documentacion Regional "Juan Bautista Vázquez"

Biblioteca Campus Central Biblioteca Campus Salud Biblioteca Campus Yanuncay
Av. 12 de Abril y Calle Agustín Cueva, Telf: 4051000 Ext. 1311, 1312, 1313, 1314. Horario de atención: Lunes-Viernes: 07H00-21H00. Sábados: 08H00-12H00 Av. El Paraíso 3-52, detrás del Hospital Regional "Vicente Corral Moscoso", Telf: 4051000 Ext. 3144. Horario de atención: Lunes-Viernes: 07H00-19H00 Av. 12 de Octubre y Diego de Tapia, antiguo Colegio Orientalista, Telf: 4051000 Ext. 3535 2810706 Ext. 116. Horario de atención: Lunes-Viernes: 07H30-19H00