Logo Repositorio Institucional

Please use this identifier to cite or link to this item: http://dspace.ucuenca.edu.ec/handle/123456789/41459
Title: Experimental Evaluation of Tubular Flocculator Implemented in the Field for Drinking Water Supply: Application in the Developing World
Authors: Trelles Agurto, Alex Fabricio
Mendez Heredia, Angel Olmedo
Garcia Avila, Fausto Fernando
Heredia Cabrera, Gina Catalina
Tonon Ordoñez, Maria Dolores
Criollo Illescas, Freeddy Adrian
Alfaro Paredes, Emigdio Antonio
Sanchez Cordero, Esteban Remigio
metadata.dc.ucuenca.correspondencia: Garcia Avila, Fausto Fernando, garcia10f@hotmail.com
Keywords: Tubular flocculator
Drinking water
Enhanced flocculation
Turbidity removal
Rural communities
metadata.dc.ucuenca.areaconocimientofrascatiamplio: 2. Ingeniería y Tecnología
metadata.dc.ucuenca.areaconocimientofrascatidetallado: 2.11.2 Otras Ingenierias y Tecnologías
metadata.dc.ucuenca.areaconocimientofrascatiespecifico: 2.11 Otras Ingenierias y Tecnologías
metadata.dc.ucuenca.areaconocimientounescoamplio: 07 - Ingeniería, Industria y Construcción
metadata.dc.ucuenca.areaconocimientounescodetallado: 0711 - Ingeniería y Procesos Químicos
metadata.dc.ucuenca.areaconocimientounescoespecifico: 071 - Ingeniería y Profesiones Afines
Issue Date: 2023
metadata.dc.ucuenca.volumen: Volumen 15, número 5
metadata.dc.source: Water S.A.
metadata.dc.identifier.doi: 10.3390/w15050833
metadata.dc.type: ARTÍCULO
Abstract: 
The purpose of this study was to evaluate the efficiency of a large-scale Horizontal Tubular Flocculator (HTF) as an easy-to-implement technology for potable water provision compared to the efficiency of a traditional baffle flocculator. The HTF was built with a 4-inch diameter PVC pipe and coupled to a sedimentation and filtration process. Experimental tests were performed using lengths of 68.4 m and 97.6 m for the HTF. These lengths were combined with raw water flow rates of 0.25, 0.5, 0.75, 1, and 2 L/s and five turbidity ranges <10 NTU, 10–20 NTU, 21–50 NTU, 51–100 NTU, >100 NTU, giving a total of 100 tests for one year. Jar tests were performed to determine the optimal dose of aluminum sulfate used as a coagulant. Hydraulic characteristics such as time of retention (TR) and velocity gradient (G) were evaluated; likewise, plug flow, dead volume, and short-circuit ratios were determined by tracer tests using the Wolf–Resnick model. The average results determined a removal of 98.8% of turbidity and 99.93% of color. The TR varied between 4.62 and 36.97 min and G varied between 6.15 and 109.62 s−1. The results showed that HTF can be useful as a flocculation unit in a purification system.
URI: http://dspace.ucuenca.edu.ec/handle/123456789/41459
https://www.mdpi.com/2073-4441/15/5/833
metadata.dc.ucuenca.urifuente: https://www.mdpi.com/2073-4441/15/5/833
ISSN: 2073-4441
Appears in Collections:Artículos

Files in This Item:
File SizeFormat 
documento.pdf3.03 MBAdobe PDFView/Open


This item is protected by original copyright



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

 

Centro de Documentacion Regional "Juan Bautista Vázquez"

Biblioteca Campus Central Biblioteca Campus Salud Biblioteca Campus Yanuncay
Av. 12 de Abril y Calle Agustín Cueva, Telf: 4051000 Ext. 1311, 1312, 1313, 1314. Horario de atención: Lunes-Viernes: 07H00-21H00. Sábados: 08H00-12H00 Av. El Paraíso 3-52, detrás del Hospital Regional "Vicente Corral Moscoso", Telf: 4051000 Ext. 3144. Horario de atención: Lunes-Viernes: 07H00-19H00 Av. 12 de Octubre y Diego de Tapia, antiguo Colegio Orientalista, Telf: 4051000 Ext. 3535 2810706 Ext. 116. Horario de atención: Lunes-Viernes: 07H30-19H00