dc.description | Los sistemas eléctricos de potencia a nivel mundial, tienden a tener responsabilidad ambiental y soberanía energética, con la incorporación de energía renovables no convencionales e ingresando problemáticas de índole técnico - operativo. Al Sistema Nacional Interconectado Ecuatoriano (SNI) se analizó considerando el caso base y 4 escenarios; el caso base establece el sistema actual con generación térmica, hidráulica y eólica con 66.6MW y una demanda del sistema de 4261.20MW, se cubrió la demanda con una aportación de 91% de generación hidráulica, 8% de térmica y 1% de eólica; en el escenario 3 con una penetración de generación eólica de 647.19MW, la salida de la unidad U6 de la central Paute Molino y una demanda de 4261.20MW, se cubrió la demanda con 79% hidráulica, 7% térmica y 13% eólica, incumpliendo los límites de frecuencia permitidos por los entes de regulación en un 0.25%; para el escenario 4 considera una penetración de generación eólica de 885.10MW, salida de la unidad U6 de la central Paute Molino y una demanda de 4261.20MW cubierta con 71% hidráulica, 8% térmica y 20% eólica incumpliendo los límites de frecuencia permitidos por los entes de regulación en un 3.5%. Se realiza simulaciones en Simulink Matlab con: Criterios del caso base y los 4 escenarios considerados, agentes de generación más representativos del SNI ecuatoriano y un sistema de contribución al Control Primario de Frecuencia (CPF) para la generación eólica con inercial virtual; se obtiene mejoras importantes en el aporte a la CPF por el agente de generación eólica. | en_US |
dc.description.abstract | Electrical power systems worldwide tend to have environmental responsibility and energy sovereignty, with the incorporation of non-conventional renewable energy and introducing technical-operational problems. The Ecuadorian National Interconnected System (SNI) was analyzed considering the base case and 4 scenarios; The base case establishes the current system with thermal, hydraulic and wind generation with 66.6MW and a system demand of 4261.20MW, the demand was covered with a contribution of 91% hydraulic generation, 8% thermal and 1% wind; In scenario 3 with a wind generation penetration of 647.19MW, the output of unit U6 of the Paute Molino plant and a demand of 4261.20MW, the demand was covered with 79% hydraulic, 7% thermal and 13% wind, failing to comply the frequency limits allowed by regulatory entities at 0.25%; For scenario 4, it considers a wind generation penetration of 885.10MW, output from unit U6 of the Paute Molino plant and a demand of 4261.20MW covered with 71% hydraulic, 8% thermal and 20% wind, failing to comply with the frequency limits allowed by regulatory entities by 3.5%. Simulations are carried out in Simulink Matlab with: Base case criteria and the 4 scenarios considered, generation agents most representative of the Ecuadorian SNI and a contribution system to the Primary Frequency Control (CPF) for wind generation with virtual inertial; Important improvements are obtained in the contribution to the CPF by the wind generation agent. | en_US |
dc.description.uri | 0000-0001-5633-1480 | en_US |
dc.format | application/pdf | en_US |
dc.format.extent | 136 páginas | en_US |
dc.language.iso | spa | en_US |
dc.publisher | Universidad de Cuenca | en_US |
dc.relation.ispartof | TM4;2460 | - |
dc.rights | Attribution-NonCommercial-NoDerivatives 4.0 Internacional | * |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/4.0/ | * |
dc.subject | Ingeniería Eléctrica | en_US |
dc.subject | Potencia eléctrica | en_US |
dc.subject | Soberanía energética | en_US |
dc.subject.other | Clasificación de la Investigación::Ingeniería Eléctrica | en_US |
dc.title | Análisis de estabilidad de frecuencia del sistema eléctrico ecuatoriano incorporando generación eólica con escenarios de demada, generación y contingencias | en_US |
dc.title.alternative | ANÁLISIS DE ESTABILIDAD DE FRECUENCIA DEL SISTEMA ELÉCTRICO ECUATORIANO INCORPORANDO GENERACIÓN EÓLICA CON ESCENARIOS DE DEMANDA, GENERACIÓN Y CONTINGENCIAS | en_US |
dcterms.description | Magíster en Electricidad mención Redes Eléctricas Inteligentes | en_US |
dcterms.spatial | Cuenca, Ecuador | en_US |
dc.rights.accessRights | openAccess | en_US |
Appears in Collections: | Tesis Maestrías |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
Trabajo-de-Titulación.pdf | Versión presentada (texto completo) | 14.33 MB | Adobe PDF | View/Open |
This item is protected by original copyright |
This item is licensed under a Creative Commons License
Centro de Documentacion Regional "Juan Bautista Vázquez" | ||||||||||
|