Logo Repositorio Institucional

Please use this identifier to cite or link to this item: http://dspace.ucuenca.edu.ec/handle/123456789/27122
Full metadata record
DC FieldValueLanguage
dc.contributor.advisorRivera Alvarado, Ricardo Fabiánes_ES
dc.contributor.authorSierra Zeas, Juan Pablo-
dc.date.accessioned2017-04-04T12:09:14Z-
dc.date.available2017-04-04T12:09:14Z-
dc.date.issued2017-
dc.identifier.urihttp://dspace.ucuenca.edu.ec/handle/123456789/27122-
dc.descriptionEl objetivo de este estudio consistió en realizar la medición y evaluación del confort lumínico, sonoro y térmico a los que están expuestos los trabajadores administrativos de la constructora China Gezhouba Group Company; se inicia el estudio con la ayuda de información de identificación de peligros y evaluación de riesgos, del Departamento SGCAS de la constructora; una vez seleccionados los puestos, se realizó in situ la medición de los parámetros y de acuerdo a lo establecido por las siguientes normas y método: Para la evaluación del confort lumínico se utilizó la norma UNE-EN 12464-1:2011, que establece los valores mínimos de iluminación para espacios en interiores, encontrándose que ningún puesto cumplía con los niveles de iluminación establecidos. Para el confort sonoro, se utilizó la Nota Técnica de Prevención # 794, Evaluación de la interferencia en la Comunicación: Método SIL; sabiendo que el ruido existente no implica una afectación para los trabajadores, se comprobó que la mayoría de puestos de trabajo a excepción del Médico ocupacional, no cumplían con las distancias mínimas requeridas, establecidas en el método. Finalmente para evaluar el confort térmico se utilizó el índice de valoración medio de fanger; comprobándose que el confort está dentro de los intervalos establecidos; sin embargo la humedad relativa está por encima de lo que establece el Real Decreto 486/1997, disposiciones mínimas de seguridad y salud en los lugares de trabajo; debiendose establecer controles operativos para este parámetro.es_ES
dc.description.abstractThe aim of this study was to perform the measurement and evaluation of lighting, sound and thermal comfort to those who are exposed administrative workers of the construction company China Gezhouba Group Company; The study begins with the help of information Hazard identification and risk assessment, the Department of the construction SGCAS; once selected positions, performed in situ measurement of parameters and according to the provisions of the following standards and methods: The standard was used for evaluation of lighting comfort UNE-EN 12464-1: 2011, which establishes the minimum lighting values for indoor spaces, finding that no post met the set lighting levels. For acoustic comfort, Prevention Technical Note # 794, Evaluation of interference in the communication was used: SIL Method; knowing that the existing noise does not imply an affectation for workers, it was found that most jobs except the occupational physician, did not meet the required minimum distances established in the method. Finally, to evaluate the thermal comfort index fanger average valuation was used; proving that comfort is within prescribed intervals; however the relative humidity is above what established by Royal Decree 486/1997, minimum safety and health in the workplace; BUT board establish operational controls for this parameter.es_ES
dc.formatapplication/pdfes_ES
dc.language.isospaes_ES
dc.relation.ispartofseriesTM4;1148-
dc.subjectConfort Luminicoes_ES
dc.subjectConfort Termicoes_ES
dc.subjectConfort Sonoroes_ES
dc.subjectHumedad Relativaes_ES
dc.subjectTesis De Maestria En Seguridad E Higiene Industriales_ES
dc.titleMedición y evaluación del confort lumínico, térmico y sonoro al que esta expuesto el personal administrativo de la Constructora China Gezhouba Group Companyes_ES
dc.typemasterThesises_ES
dc.ucuenca.paginacion113 páginases_ES
dc.description.degreeMagíster en Seguridad e Higiene Industriales_ES
dc.description.cityCuencaes_ES
dc.ucuenca.idautor1309099586es_ES
dc.cedula.director0103012092es_ES
Appears in Collections:Tesis Maestrías

Files in This Item:
File Description SizeFormat 
Tesis.pdftexto completo4.13 MBAdobe PDFThumbnail
View/Open


This item is protected by original copyright



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

 

Centro de Documentacion Regional "Juan Bautista Vázquez"

Biblioteca Campus Central Biblioteca Campus Salud Biblioteca Campus Yanuncay
Av. 12 de Abril y Calle Agustín Cueva, Telf: 4051000 Ext. 1311, 1312, 1313, 1314. Horario de atención: Lunes-Viernes: 07H00-21H00. Sábados: 08H00-12H00 Av. El Paraíso 3-52, detrás del Hospital Regional "Vicente Corral Moscoso", Telf: 4051000 Ext. 3144. Horario de atención: Lunes-Viernes: 07H00-19H00 Av. 12 de Octubre y Diego de Tapia, antiguo Colegio Orientalista, Telf: 4051000 Ext. 3535 2810706 Ext. 116. Horario de atención: Lunes-Viernes: 07H30-19H00